AVI HOOD ELECTRICAL REQUIREMENTS
Inputs into Junction Box
The AVI Hood system provides:
Three (3) switching outputs for HVAC dampers and dedicated units
One (1) 230 VAC, 10 Amp, variable frequency, three phase power output for the ventilation
exhaust fan.
Up to Three (3) receptacles for ovens.
One (1) 120 VAC fire alarm signal for Standard hoods, or one (1) 24 VAC fire alarm signal for
World Hoods
Outputs from Junction Box
# of Circuits Rating Purpose
1 208/240 VAC, 1 Phase, 60 Hz, 6 Amp VFD Controller
up to 3 120 VAC, 1 Phase, 60 Hz, 20 Amp Ovens
1 120 VAC, 1 Phase, 60 Hz, 1 Amp System Power
1 230 VAC, 1 Phase, 50 Hz, 6 Amp VFD Controller
up to 3 230 VAC, 1 Phase, 50 Hz, 10 Amp Ovens
1 230 VAC, 1 Phase, 50 Hz, 1 Amp System Power
Standard
World
AVI Hood Electric Utility Specifications